Workspacecooling for Evaporative Cooling French Language version of Work Space Cooling

 

Factory cooling
Commercial cooling
Industrial cooling
Portable industrial cooling
Mobile cooling
Suppliers of EcoCooling Evaporative Cooling Units

Evaporative Cooling Configuration

Whilst it is possible to install the coolers without any modification to the control system there is the possibility to customise the performance using the dip switches contained on the printed circuit board in the control panel.

 

Evaporative Cooling configuration
Evaporative Cooling configuration

 

The default settings and their functions are shown below:

Switch
Default
Function
1
Off
Pre Cool Cycle – Allows the pad to wet for 5 minutes before fan starts
2
Off
Salinity 1
3
On
Salinity 2
4
On
Salinity 3
5
Off
24 hr dry cycle – Sets the cooler to dry out completely every 24 hrs
6
Off
Off speed 1390 On max speed 1200
7
Off
Off speed 1390 On max speed 1000
8
Off
Enables complete stop in Auto instead of remaining at speed 1/vent

Notes:

The default salinity setting is 30% bleed which is suitable for most mains water supply. Range of 18% to 56% available.

The spare output on the printed circuit board is available to control a ventilation fan which will run whenever the cooler is operational.

The LED will be display the last alarm condition should one have occurred.

go to top of page

 

 
Work Space Cooling are specialists in the cooling of industrial and commercial premises
ACHIEVE UP TO 35 KW of COOLING for 1KW OF ELECTRICITY USED
Site created by: Wyehead Design ©2005